The doors of this Lithium-Ion Battery Storage Cabinet have 2 factor latching with 3 x 304 stainless steel slam shut catches on the inside. On the outside – 2 x 304 Stainless Steel latches join the doors together to become one – mitigating the chance of the doors blowing open in a multi – battery explosion.
5 x completely insulated compartments with many adjustable positions. It is possible to remove shelves to fit your larger batteries.
10 x one way vents – made up of a 100mm diameter flame arrestor on the inside wall, then a HotWall filter in the centre of the walls, then louvre exhausts – 5 on each side.
The Hydrogen gases and Hydrogen Fluoride smoke given off when batteries explode, need to escape through a one way vent to prevent pressure build up within the cabinet resulting in the doors blowing open.
Class 9 Misc DG cabinets and Flammable cabinets are not designed for battery storage, they are designed to stop sparks getting into the cabinet : Lithium-ion Battery Cabinets are designed to stop exploding batteries, sparks and extreme temperatures from getting out of the cabinet.
Powder coated with our high-build polyester resin powder for longevity and easy cleaning.






Complete technical specifications, compliance certificates, and installation guide
Thermal runaway occurs when a lithium-ion battery overheats and releases hydrogen gas, followed by hydrogen fluoride smoke, leading to an explosion within 1-3 seconds. The explosion can reach over 1000 degrees C and cause cascading failures in nearby batteries. Learn more about lithium-ion batteries and charging fire risks and the specific safety measures required.
Our HotWall insulation system completely surrounds each compartment like a kiln, with continuous ratings of 1260-1430 degrees C. This prevents heat from permeating to the cabinet’s exterior walls, protecting your facility from secondary fire disasters when thermal runaway occurs.
Check our video on how well our HotWall Extreme Temperature Insulation works.
The TSCW ventilation system safely expels hydrogen gases and hydrogen fluoride fumes through flame arrestors to exhaust vents. Without proper ventilation, pressure buildup could force cabinet doors open or create dangerous conditions. This system is critical for safe battery management.
No – regular flammable goods cabinets are not designed for lithium-ion battery risks. The unique dangers of thermal runaway, hydrogen gas emissions, and extreme temperatures require specialised containment solutions. For first-time buyers wondering about the differences, check our battery charging cabinet compliance guide.
Our cabinets accommodate 4 batteries per compartment, with total capacities ranging from 4 stations (1 compartment) to 20 stations (5 compartments). The Heavy Duty model specifically supports 48V batteries, while other models accommodate various lithium-ion battery types with their respective chargers.
Each compartment is individually insulated to contain explosions and prevent thermal runaway from spreading to neighbouring batteries. The HotWall insulation and TSCW ventilation system work together to contain the explosion, manage dangerous gases, and protect your facility from secondary fires.